25
ASEGmbH
Ludwig -Erhard -Str. 2c
D-41564Kaarst
Tel.+49 2131 40 21 30
Achse
1
2
3
4
5
6
7
8
9
10
11
12
A
1,5 Lux
1,5 Lux 3,0 Lux 12,0 Lux 15,0 Lux 13,0 Lux 13,0 Lux 15,0 Lux 13,0 Lux 14,0 Lux 15,0 Lux 13,0 Lux
B
2,0 Lux
1,8 Lux 3,0 Lux 14,0 Lux 20,0 Lux 15,0 Lux 16,0 Lux 20,0 Lux 16,0 Lux 17,0 Lux 20,0 Lux 15,0 Lux
C
20,0 Lux 18,0 Lux 8,0 Lux 10,0 Lux 10,0 Lux 10,0 Lux 10,0 Lux 20,0 Lux 16,0 Lux 17,0 Lux 20,0 Lux 15,0 Lux
D
16,0 Lux 10,0 Lux 8,0 Lux 10,0 Lux 10,0 Lux 10,0 Lux 10,0 Lux 20,0 Lux 16,0 Lux 17,0 Lux 18,0 Lux 14,0 Lux
E
20,0 Lux 20,0 Lux 18,0 Lux 10,0 Lux 20,0 Lux 16,0 Lux 15,0 Lux 18,0 Lux 20,0 Lux 17,0 Lux 26,0 Lux 15,0 Lux
F
20,0 Lux 18,0 Lux 8,0 Lux 10,0 Lux 10,0 Lux 10,0 Lux 10,0 Lux 20,0 Lux 16,0 Lux 17,0 Lux 20,0 Lux 29,0 Lux
G
28,0 Lux 20,0 Lux 20,0 Lux 25,0 Lux 18,0 Lux 24,0 Lux 21,0 Lux 20,0 Lux 25,0 Lux 21,0 Lux 20,0 Lux 15,0 Lux
E-m
15,3 Lux
E-min
1,5 Lux
E-max
29,0 Lux
Manuelle Notlichtberechnung
Herr Mustermann
Herr Musterfrau
Gesamtergebnis:
Wiederkehrende Prüfung
Bemerkung:
Notwendige Beleuchtungsstärke
wird erreicht
Verwendete Messgeräte:
Raumnummer:
Prüfprotokoll-Nr.
Projekt:
Achsenabstand:
Grund der Prüfung:
Prüfer 2:
Prüfer 1:
261055-08
A 1201 - Speiseraum
2m x 2m
Für dieseNotlichtberechnungstabelle
behaltenwir alleRechte vor.
OhneunsereZustimmungdarf sieweder vervielfältigtnochDritten zugängiggemachtwerden.
TECHNIK
KNOW-HOW
SERVICE
Untersuchungsbericht
Berichtsdatum
23.12.2015
Unternehmen
ASE GmbH Kaarst
Kunde
Muster GmbH
Adresse
Ludwig-Erhard-Str. 2c
Adresse
Musterstr.99
Thermograf
Szymkowiak
Ansprechpartner
Herr Mustermann
Beschreibung
FLIR InfraCAM Wester
Kameramodell
20.03.2015 07:59:46
Bilddatum
IR_0353.jpg
Bildname
0,78
Emissionsgrad
21,0 °C
Reflektierte
Temperatur
2,0 m
Objektabstand
Beschreibung
FLIR InfraCAM Wester
Kameramodell
20.03.2015 08:05:34
Bilddatum
IR_0363.jpg
Bildname
0,78
Emissionsgrad
21,0 °C
Reflektierte
Temperatur
2,0 m
Objektabstand
1 (2)