BUS CABLE INSTALLATION (EXAMPLE)
Bus-mains monitoring module –
Connected in series
Lenght and quantity depend on
the cable cross section. Example:
Assuming a cable cross section of
4x0.25² and a lenght of 400 m you
can connect up to seven modules.
Spur line cable max. 2 m
Total Bus cable length up to 1000 m
Bus-mains monitoring module
Bus-mains monitoring module
Bus-mains monitoring module
Mains + 5 free Inputs
LAN CAT 7
Connection of a second
control and display unit
to remotely operate the
system, i.e. from the
caretakers office
2 Bus connections per system
Utilizing a 4 x multiplexer the
max. possible bus cable length
becomes 4 x 1000 m
Power supply to the sub- stations
by means of
one
cost-saving
supply line in maintained function
mode (NHX 30/ 90 min)